Description:
The main causes of compressor liquid hammer damage are as follows:
When a large amount of liquid is returned to the compressor, the droplet will have a great impact on the vortex disc during the compression process, which may break the vortex disk; the lubricating oil containing a large amount of liquid refrigerant has low viscosity, and can not form enough oil film on the friction surface, resulting in the rapid wear of the internal moving parts of the compressor; in addition, the refrigerant in the lubricating oil will boil when encountering heat in the transportation process, affecting the normal transportation of lubricating oil.
After liquid hammer, the fragments of the scroll plate fall on the coil and damage the coil insulation layer, which may lead to current protection or compressor built-in protection.
Compressor can run, but no exhaust, no high voltage, low current, abnormal sound. If the sound of compressor is abnormal or the compressor shaft is stuck, the current protection or air switch trip will occur as soon as the compressor is started.
|
Product name |
Hermetic Scroll Compressor |
|
Model |
ZP144KCE-TFD-522 |
|
Brand |
Copeland |
|
Refrigerant |
R410A |
|
MOQ |
1 piece |
|
Application |
Heat pump and Air Conditioning |


Hot Tags: great air conditioning compressor zp144kce, manufacturers, suppliers, factory, cheap, in stock, Low Temperature CPL Scroll Compressor, 40HP CPL Refrigeration Compressor, CPL Compressor For Refrigeration Unit, Low Temperature Scroll CPL Compressor, ZSI CPL Compressor With Low Temperature, CPL Refrigeration Compressor