Can a Danfoss MT Compressor Be Replaced With an MTZ Model?
Nov 16, 2026
1. What Is the Difference Between Danfoss MT and MTZ Compressors?
Both are Maneurop hermetic reciprocating compressors, but their refrigerant applications and factory oil charges are different.
| Specification | MT Series | MTZ Series |
|---|---|---|
| Factory oil | 160P Mineral Oil | 175PZ POE Oil |
| Main applications | R22 | Approved HFC/HFO refrigerants |
Common MTZ refrigerants include R134a, R404A, R407C, R448A, R449A, R452A and R513A. Approval depends on the specific model and operating conditions.
2. Can an MTZ Compressor Directly Replace an MT Compressor?
No, not in its original factory configuration.
Take MT64-4VI and MTZ64-4VI as an example. These are corresponding models with similar mechanical configurations, but their factory oil charges are different:
-
MT64-4VI: Supplied with 160P mineral oil for its R22 application.
-
MTZ64-4VI: Supplied with 175PZ POE oil for its approved refrigerant applications.
Although the two models share the same mechanical platform, this does not mean they can be installed interchangeably without considering the refrigerant and lubricant.
3. Can an MT Compressor Be Converted to an MTZ Configuration?
Yes. Danfoss has published an oil-conversion procedure for compatible MT and MTZ models.
The conversion involves removing the original oil and replacing it with the correct lubricant for the intended refrigerant application.
One important detail: older Danfoss conversion documents refer to 160PZ oil, while the current MTZ application guide specifies 175PZ. The current oil specification and model-specific conversion requirements should be followed.
An oil change alone does not automatically make every MT compressor suitable for every MTZ refrigerant application.
4. What Should Be Checked Before Replacing an MT Compressor?
Before selecting an MTZ replacement, check these four points:
-
Refrigerant: Is the intended refrigerant approved for the compressor model?
-
Lubricating oil: Is the correct oil type and grade being used?
-
Cooling capacity: Does the replacement provide sufficient capacity at the required evaporating and condensing temperatures?
-
Electrical specifications: Do the voltage, frequency and motor configuration match the existing system?
If these specifications are not compatible, a compressor with the same nominal capacity may still be unsuitable.
Conclusion
For an existing R22 system using an MT compressor with mineral oil, the correct MT configuration is generally the straightforward replacement choice.
If an MTZ compressor is being considered, the refrigerant application and oil configuration must be addressed first. A conversion may be possible for compatible models, but it must follow Danfoss' current requirements.